Vol.4 , No. 6, Publication Date: Nov. 9, 2017, Page: 59-66
[1] | Mohamed EL-Shimy, Electrical Power and Machines Department, Ain Shams University (ASU), Abbassia, Cairo, Egypt. |
[2] | Mohamed Abdelraheem Badr, Electrical Power and Machines Department, Faculty of Engineering, Future University in Egypt (FUE), New Cairo, Egypt. |
[3] | Mai Kelany, Engineering Contracting Company, Cairo, Egypt. |
The analysis of reactive demands of high voltage transmission links connecting wind farms to the central grid is considered in this paper. Both High Voltage Alternating Current (HVAC), and High Voltage Direct Current (HVDC) options as well as overhead, and cable transmission alternatives are considered in the analysis. Therefore, the presented work is applicable for both onshore, and offshore installations considering various transmission technologies. The sizing of the required reactive power compensators for the transmission system is the main objective of the manuscript. The target is to keep acceptable operating voltage limits through appropriate amounts of reactive power injection or absorption at the wind farms interface bus. The considered wind farm is made up with Doubly Fed Induction Generators (DFIGs). Based on the reactive power capability limits of the DFIGs comprising the wind farm, the minimum rating, and type of external reactive power compensating devices are determined for various transmission options. In addition, the reactive power loading on the compensators at various operating conditions of the wind farm is determined. The salient conclusions are listed in the results, and conclusions sections.
Keywords
Wind Power, DFIG, Transmission Alternatives, Loading Capability Limits, Reactive Power Compensators
Reference
[01] | M. El-Shimy, “Reactive power management and control of distant large-scale grid-connected offshore wind power farms,” International Journal of Sustainable Energy, vol. 32, no. 5, pp. 449-465, 2013. |
[02] | M. EL-Shimy, “Modeling and analysis of reactive power in grid-connected onshore and offshore DFIG-based wind farms,” Wind Energy, vol. 17, no. 2, pp. 279–295, 2014 |
[03] | O. Gomis-Bellmunt, J. Liang, J. Ekanayake et al., “Topologies of multiterminal HVDC-VSC transmission for large offshore wind farms,” Electric Power Systems Research, vol. 81, no. 2, pp. 271-281, 2011. |
[04] | S. Lumbreras, and A. Ramos, “Offshore wind farm electrical design: a review,” Wind Energy, vol. 16, no. 3, pp. 459-473, 2013. |
[05] | S. Lumbreras, and A. Ramos, “Optimal design of the electrical layout of an offshore wind farm applying decomposition strategies,” IEEE Transactions on Power Systems, vol. 28, no. 2, pp. 1434-1441, 2013. |
[06] | N. Barberis Negra, J. Todorovic, T. Ackermann, "Loss evaluation of HVAC and HVDC transmission solutions for large offshore wind farms," Electric Power Systems Research, vol. 76, pp. 916–927, 2006. |
[07] | F. Renaudin, "Integration and Stability of a Large Offshore Wind Farm with HVDC Transmission in the Norwegian Power System," Master of Science in Electric Power Engineering, Norwegian University of Science and Technology, 2009. |
[08] | P. Bresesti, W. L. Kling, R. L. Hendriks, and R. Vailati., "HVDC Connection of Offshore Wind Farms to the Transmission System," IEEE transactions on energy conversion, VOL. 22, NO. 1, vol. 22, March 2007. |
[09] | J. Schachner, "Power Connections for Offshore Wind Farms," Diploma Thesis, Department of Electrical Engineering, University of Leoben, Austria, 2004. |
[10] | A. Kusiak and Z. Song, "Design of wind farm layout for maximum wind energy capture," Renewable Energy vol. 35, pp. 685-694, 2010. |
[11] | G. Marmidis, S. Lazarou, E. Pyrgioti, "Optimal placement of wind turbines in a wind park using Monte Carlo simulation," Renewable Energy vol. 33, pp. 1455–1460, 2008. |
[12] | S. Lundberg, "Evaluation of wind farm layouts," Europian Power Electroics and Drives (EPE) vol. 16, 2006. |
[13] | S. Lundberg, "Wind Farm Configuration and Energy Efficiency Studies - Series DC versus AC Layouts," Thesis for the degree of doctor of philosophy, Department of Energy and Environment, Chalmers University of Technology, Sweden, 2006. |
[14] | A. Emami and P. Noghreh, "New approach on optimization in placement of wind turbines within wind farm by genetic algorithms," Renewable Energy vol. 35, pp. 1559-1564, 2010. |
[15] | L. Lazaridis, “Economic Comparison of HVAC and HVDC Solutions for Large Offshore Wind Farms under Special Consideration of Reliability Lazaros P. Lazaridis,” PhD thesis, Royal Institute of Technology: Stockholm, 2005. |
[16] | New & Renewable Energy Authority (NREA). Available at: http://nrea.gov.eg/english1.html |
[17] | M. Ahmed, M. EL-Shimy, and M. Badr, “Advanced modeling and analysis of the loading capability limits of doubly-fed induction generators,” Sustainable Energy Technologies and Assessments, vol. 7, pp. 79-90, 2014. |
[18] | Power System Analaysis Toolbox (PSAT). Available at: http://faraday1.ucd.ie/psat.html |
[19] | PSAT manual. Available at: http://licence.ucd.ie/tech/500 |
[20] | F. Milano, “Power system modelling and scripting”, Springer Science & Business Media, 2010. |
[21] | P. Kundur, “Power system stability and control”. Edited by Neal J. Balu, and Mark G. Lauby. Vol. 7. New York: McGraw-hill, 1994. |
[22] | N. Barberis, J. Todorovic, and T. Ackermann. "Loss evaluation of HVAC and HVDC transmission solutions for large offshore wind farms." Electric Power Systems Research, Vol. 76, No. 11, 2006, pp. 916-927. |